Data center chillers, compared

This table compares data center chillers from 32 vendors. The largest single unit listed is 21 MW (Trane), 23 vendors offer free cooling, 22 use oil-free compressors and 10 position a line for AI halls. Every figure links to the vendor’s own page.

32 vendors 63 sources

Last verified

Psychrometric chart with vendor supply water temperatures A psychrometric chart from 0 to 50 degrees Celsius. Blue ticks mark the highest chilled-water supply temperature each vendor states, from 20 to 35 degrees Celsius. 0 10 20 30 40 °C 20 °C: Swegon (BlueBox) 20 25 °C: STULZ 25 26 °C: Airedale by Modine, Mitsubishi Electric (Climaveneta) 26 28 °C: Blue Star 28 29.4 °C: Daikin Applied 29.4 30 °C: Aermec, Johnson Controls (YORK) 30 33 °C: Uniflair (Schneider Electric) 33 35 °C: Carrier, Thermax 35
Blue dots: the highest supply water temperature each vendor states, 20 to 35 °C, one dot per vendor. Chillers for AI halls
Heat rejectionCompressorsRefrigerantsFree coolingAI or high-density claimEfficiency (as published)
Trane400121,0002Air- and water-cooledOil-free magnetic-bearing centrifugal; centrifugal; variable-speed screwR-1234ze; R-513A; R-134a; R-1233zd; R-515BYes——YesGVAF: SEER up to 6.55; seasonal metric, not full-load EER2026-11-11
Hitachi Cooling & Heating—12,3102Air- and water-cooledTwo-stage centrifugal (S, VG); oil-free magnetic-levitation (VM)R-513A; R-1233zd; R-1234ze; R-134a————Announced range: up to 13.8 ACCOP; vendor-specific annual metric2026-11-11
Daikin Applied302110,5511Air- and water-cooledVariable-volume-ratio screw; Variable-speed oil-free magnetic-bearingR-1234ze(E); R-515B; R-513A; R-1233zd(E)Yes29.41——Pathfinder AWV: IPLV above 22 EER; Pathfinder AWM: up to 22.7 IEER (US units)2026-11-11
Thermax176110,5511Absorption———351——E2 thermal COP 1.1–1.53; heat-input metric, not electric EER2026-11-11
Dunham-Bush264110,5501Air- and water-cooledInverter-driven dual-stage, oil-free magnetic-bearingR-134a; R-513A—————2026-11-11
Haier44018,7931Water-cooledDirect-drive magnetic-bearing centrifugalR-134a———Yes—2026-11-11
Vertiv30016,0004Air- and water-cooledInverter screw; oil-free magnetic-levitation centrifugalR-1234ze; R-513A; R-515B; R-134aYes——Yes—2026-11-11
Kirloskar Chillers33414,2201—Magnetic-bearing centrifugalR-134a; R-1234ze—————2026-11-11
Carrier17013,8001Air- and water-cooledScroll; variable-speed screw; two-stage magnetic-bearing centrifugalR-513A; R-1234ze(E); R-515B; R-32Yes3531802YesCOP 6.75, IPLV 11.4 under AHRI (AquaEdge 19MV4)2026-11-11
Johnson Controls (YORK)88043,5004Air-cooledSingle-stage magnetic-bearing centrifugal, variable-speedR-1234ze—3031801Yes40% less annual power than other solutions at the same capacity (vendor claim)2026-11-11
Multistack—2,9891Air-cooledTwo-stage variable-speed centrifugal MagLev—Yes————2026-11-11
Smardt21112,5001Air- and water-cooledOil-free magnetic-bearingR-513A; R-515B; R-1234ze; R-134aYes————2026-11-11
Uniflair (Schneider Electric)1,20012,5001Air-cooledOil-free magnetic-bearing centrifugal—Yes3311801YesEER 4.66 (Schneider Electric’s figure; rating conditions not published)2026-11-11
APX DCS (LFB Group)5012,4001—Oil-free centrifugal; multi-scroll; inverter screwR-1234ze; R-454BYes————2026-11-11
Midea Building Technologies56312,2511Air-cooledTwo-stage magnetic-bearing centrifugal; inverter screwR-1234ze(E); R-513AYes——YesCOP up to 7.11 at AHRI conditions (centrifugal line)2026-11-11
Geoclima (Munters)—2,2001Air-cooledOil-free centrifugal Turbocor with magnetic levitationR-513A; R-134A; R-1234zeYes———R513A/R134A example: full-load EER 5.35 at 35°C ambient and 34/24°C water2026-11-11
LG Electronics1,68812,1101Air-cooledSemi-hermetic oil-free magnetic-bearing centrifugal, variable-speedR-513AYes——YesEER 4.0 at full load, microchannel heat exchanger2026-11-11
Airedale by Modine11012,0002Air-cooledOil-free centrifugal TurbocorR-1234ze; R-134aYes262——Up to 39% energy savings over standard methods (TurboChill DCS, vendor claim)2026-11-11
ENGIE Refrigeration25012,0001Air- and water-cooledOil-free magnetic-bearing—Yes————2026-11-11
Blue Star—1,9341—Semi-hermetic screw with permanent-magnet motorsR-134a—281601——2026-11-11
STULZ28011,8601Air- and water-cooledScrew (stepless or frequency-converter); TurbocorR-1234ze; R-513AYes251———2026-11-11
Kaltra25011,8501Air-cooledScrew; scrollR-134a; R-513A; R-1234ze; R-410A; R-452B; R-454BYes————2026-11-11
Mitsubishi Electric (Climaveneta)1,20011,7501Air-cooledMagnetic-levitation centrifugal; oil-free magnetic-bearingR-1234ze; R-515BYes263—Yes—2026-11-11
Aermec20011,6001Air-cooledScrew (NSM HWT); Turbocor magnetic-levitation (TBA/TBG)R-134a; R-513A; R-1234ze; R-515B; R-32Yes301———2026-11-11
Motivair by Schneider Electric3511,5831—Screw and scroll optionsR-134a; R-410A; R-1234ze; R-513AYes————2026-11-11
Euroklimat19011,4001Air- and water-cooledOil-free magnetic-levitation TurbocorR-134a; R-513A; HFO optionYes————2026-11-11
Galletti37011,2001Air-cooledHermetic scrollR-410AYes————2026-11-11
Swegon (BlueBox)22014801Air-cooledScrollR-32Yes201———2026-11-11
Refra—4101Water-cooled—Propane R-290—————2026-11-11
Clivet——Air-cooledMagnetic, full inverter—Yes————2026-11-11
HiRef——Water-cooledScrewR-513A—————2026-11-11
Mitsubishi Heavy Industries Thermal Systems———Centrifugal—Yes——Yes—2026-11-11

Questions buyers ask

How big is a data center chiller?

Published single-unit capacities run from 35 kW (Motivair by Schneider Electric) to 21 MW. Trane lists 21 MW, Hitachi 12.3 MW and Daikin Applied 10.6 MW. Sort the table by Largest unit or filter by kW. Air-cooled and water-cooled lines are split on the air-cooled and water-cooled pages.

Which chillers make the warmest supply water for AI halls?

Carrier (35 °C), Thermax (35 °C), Uniflair (33 °C), Aermec (30 °C) state the warmest chilled-water supply, up to 35 °C. The lowest stated is 20 °C (Swegon). 10 vendors name AI, high-density or liquid-cooled data centers as a target: see chillers for AI data centers.

Which vendors offer free cooling?

23 of 32 vendors list integrated or optional free cooling, including Trane, Carrier, Vertiv, STULZ. The free-cooling list shows each vendor’s capacity range, supply temperature and refrigerant beside the label.

Which refrigerants do data center chillers use?

The refrigerant names the vendors publish: R-1234ze on 17 vendors’ lines, R-513A on 16, R-134a on 14, R-515B on 7. 22 vendors offer an HFO, HFO-blend or natural refrigerant. GWP is shown only where the vendor prints it: Airedale by Modine, Carrier, Smardt, STULZ. Vendors cite different IPCC reports, so the values are not normalised.

What is an oil-free chiller?

A chiller whose compressor runs on magnetic bearings or a Turbocor-type design, so it needs no lubricating oil. 22 vendors list one, from Smardt to Trane. See the oil-free and magnetic-bearing list.

How fast does a chiller get back to full load after a power cut?

4 vendors publish a figure: Blue Star (60 s), Carrier (180 s), Johnson Controls (180 s), Uniflair (180 s). The others publish no recovery time. Sort the table by Full-load recovery to compare.

How this table is built

Full methodology

Every value comes from the vendor’s own product page, brochure, press release or annual report. The small number next to a figure opens that source. An empty cell means the vendor does not publish the figure, and we do not estimate it.

Capacity covers every line named in the Lines field, converted to kW at 3.517 kW per ton. Each row carries the date we last checked it, newest 11 Nov 2026. Spot a stale number? Email hello@chillervendors.com with the source and we update the row.